PTE-Cable

PTE-Cable

Cable sensor for HVAC applications

PTE-Cable is a passive temperature sensor engineered for HVAC applications. PTE-Cable senses temperatures in a wide range. It is well protected from the environment by its stainless steel sleeve which is crimped on to premium quality silicone rubber cable. Inside the sleeve, the temperature sensor is protected against condensation, ensuring long service life. The cable is halogen-free and oil resistant. PTE-Cable has a high protection rating of IP67.

PTE-Cable is available with the following sensor types:

  • NTC10k
  • NTC20k
  • Pt1000
  • Ni1000
  • Ni1000-LG

Applications

DPT-Flow Series-4 devices are commonly used in HVAC/R
systems for:

• Air flow monitoring across centrifugal fans and blowers
• In-duct air flow monitoring
• VAV applications

Specifications

Performance

Accuracy (at applied pressure):
Ranges < 0.5 inWC = ±0.01 inWC
Ranges  0.5 inWC = ±1.5 % inWC
(Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error).
Thermal effects:
Temperature compensated across the full spectrum of capability.
Overpressure:
Proof Pressure: 100 inWC
Zero point calibration:
Automatic with function or manual pushbutton autozero
Response time:
1.0−20 sec, selectable via menu

Technical Specifications

Media compatibility:
Dry air or non-aggressive gases
Pressure units (select via configuration menu):
Pa, kPa, mbar, inWC, mmWC
Pressure output range (select via configuration menu)

  DPT-Flow-4 DPT-Flow-8 DPT-Flow-20 DPT-Flow-30
Pa 100-1,000 200-2,000 500-5,000 700-7,000
kPa 0.1-1.0 0.2-2.0 0.5-5.0 0.7-7.0
mbar 1-10 2.0-20 5.0-50 7.0-70
mmWC 10-100 20-200 50-500 70-700
inWc 0.4-4.0 0.8-8.0 2.0-20 2.5-30

Flow units (select via configuration menu):
Volume: m3/s, m3/hr, cfm, l/s
Velocity: m/s, fpm
Flow output range (select via configuration menu):

Units Range
m3/s 0.025-50
m3/hr 100-200,000
cfm 50-100,000
l/s 25-50,000
m/s 1-100
ft/min 200-20,000

Measuring element:
MEMS
Environment:
Operating temperature:
14−122 °F (-10−50 °C)
with (-eZ) circuit option
23−122 °F (-5−50 °C)
Configuration, while using display
32−122 °F (0−50 °C)
Storage Temperature:
-4−158 °F (-20−70 °C)
Humidity:
0 to 95 % rH, non condensing

Physical

Case:
Dimensions: 3.54” x 3.74” x 1.4”
(90.0 x 95.0 x 36.0 mm)
Weight: 5.3 oz (150 g)
Mounting:
2 each 11/64” (4.3 mm) screw holes, one slotted
Materials:
Case: ABS (UL 94 V-0 Approved)
Lid: PC (UL 94 V-1 Approved)
Protection standard:
IP54 / NEMA3
Display (required for configuration):
2-line display (12 characters/line)
Size: 1.81” W x 0.57” H
(46.0 x 14.5 mm)
Electrical connections:
4-screw terminal block
Wire: 12–24 AWG (0.2–1.5 mm2)
Cable entry:
Strain relief: M16
Knockout ø: 0.625” (16 mm)
Pressure fittings:
3/16” ø (5.2 mm) barbed brass
+ High pressure
− Low pressure

Electrical

Voltage:
Circuit: 3-wire ([V out or P out], 24 V, GND)
Input: 24 VAC or VDC, ±10 %
Output: 0–10 V, selectable via jumper
Power consumption: <1.0 W
Resistance minimum: 1 kΩ
Current:
Circuit: 3-wire ([V out or P out], 24 V, GND)
Input: 24 VAC or VDC, ±10 %
Output: 4–20 mA, selectable via jumper
Power consumption: <1.2 W
Maximum load: 500 Ω

Conformance

Meets requirements for CE marking:
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU

Meets safety requirements for electrical equipment for measurement, control, and laboratory use:
ETL marking, standard IEC61010-1.

Product is tested and meets the NRTL product
approval requirements.

 

Model summary

  DPT-Flow-4 DPT-Flow-8 DPT-Flow-20 DPT-Flow-30
Measurement ranges (inWC) 0–4 0–8 0–20 0–30
Description Model # Part # Model # Part # Model # Part # Model # Part #
Flow transmitter for measuring airflow in-duct and on centrifugal fans                
– with display DPT-Flow-4-D
Series 4
10156 DPT-Flow-8-D
Series 4
10158 DPT-Flow-20-D
Series 4
10160 DPT-Flow-30-D
Series 4
10162
– with and display DPT-Flow-4-eZ-D
Series 4
10157 DPT-Flow-8-eZ-D
Series 4
10159 DPT-Flow-20-eZ-D
Series 4
10161 DPT-Flow-30-eZ-D
Series 4