AVT

The AVT is an electronic air velocity and temperature transmitter for air and non-combustible gases with optional relay output

AVT series air velocity transmitters are engineered for building automation in the HVAC/R industry. The AVT measures air velocity and temperature, with field selectable range and output options in a single device. Designed with a duct mount probe and adjustable collar suitable for round or rectangular ducts. The collar allows incremental adjustments to the insertion depth, enabling fine-tuning of measurement results to conform test and balance data.

AVT series devices include:
• Three (3) field selectable measurement ranges for air velocity, selectable via jumper, see Model Summary.
• Separate readings and outputs for air velocity and temperature.
• Output options include: voltage (0–10 V) and current (4–20 mA).

AVT series device offers:
• LCD display
• Field adjustable relay
• NIST-calibration documentation.

The versatility of the AVT series air velocity and temperature transmitters delivers the right product for your automation application.

Comments are closed.

Applications

AVT series devices are commonly used in HVAC/R systems for:
• In-duct air flow and velocity monitoring
• In-duct temperature monitoring
• VAV applications

Specifications

Performance

Measurement ranges:
Velocity:
Range 2: 0–400 fpm
Range 10: 0–2,000 fpm
Range 20: 0–4,000 fpm
Temperature: 32−122 °F (0−50 °C)
Accuracy:
Velocity:
Range 2: 0–400 <20 fpm +5 % from reading
Range 10: 0–2,000 fpm <100 fpm +5 % from reading
Range 20: 0–4,000 fpm <200 fpm +5 % from reading
Temperature: <0.9 ºF for v > 100 fpm
Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error.

Technical Specifications

Media compatibility:
Dry air or non-aggressive gases
Measuring units:
fpm and °F
Measuring element:
Temperature: ntc10k
Velocity: Pt1000
Environment:
Operating temperature: 32−122 °F (0−50 °C)
Storage temperature: -4−158 °F (-20−70 °C)
Humidity: 0 to 95 % rH, non condensing
Physical
Case:
Dimensions: 3.54” x 3.74” x 1.4”
(90.0 x 95.0 x 36.0 mm)
Dimensions – Probe:
OD: 0.394 in (10 mm)
Length: 8.26 in (210 mm) from bottom of the cover
Immersion length with flange: Adjustable 2”–7.08”
(50–180 mm)
Weight (Case + Probe):
7.76 oz (220 g)
Mounting:
2 screw holes, 11/64” (4.0 mm)
Materials:
Case: ABS (UL 94 V-0 Approved)
Lid: PC (UL 94 V-1 Approved)
Probe: Stainless Steel
Protection standard:
IP54 / NEMA3
Display
3 1/2 digit LCD display
Size: 1.8” x 0.5” (45.7 x 12.7 mm)
Electrical connections: (2 each)
Power supply & signal out: 4-screw terminal block
12–24 AWG (0.2–1.5 mm2)
Relay out: 3-screw terminal block
12–24 AWG (0.2–1.5 mm2)
Cable entry: (2 each)
Strain relief: M16
Knockout : 0.625” (16 mm)

Electrical

Input: 24 VDC / 24 VAC ± 10 %
Current consumption 35 mA (50 mA with relay) +
40 mA with mA outputs
Output signal 1: (temperature out)
0–10 V (linear to temperature)
L min 1 kΩ
4–20 mA (linear to temperature)
L max 400 Ω
Output signal 2: (velocity out)
0–10 V (linear to fpm)
L min 1 kΩ
4–20 mA (linear to fpm)
L max 400 Ω
Relay Out: 3 screw terminal block
(NC, COM, NO)
12–24 AWG (0.2–1.5 mm2)
Potential free SPDT
250 VAC, 6 A / 30 VDC, 6 A adjustable switching point
and hysteresis

Conformance

Meets requirements for CE marking:
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU

Meets safety requirements for electrical equipment for measurement, control, and laboratory use:
ETL marking, standard IEC61010-1.

Product is tested and meets the NRTL product approval requirements.

 

Model summary

Measurement ranges:
Velocity f/m
Temperature °F
(field selectable via jumper)
0–400 / 0–2000 / 0–4000 f/m
32–122 °F
 
Description Model# Part#
All-in-one air velocity transmitter AVT 10082
– with display AVT-D 10083
– with display and relay AVT-D-R 10084